  1.     SECTION 08747
  2.  
  3.     FIRE DOOR OPERATORS
  4. NOTE ** Dor-O-Matic, automatic door operators and activators.
  5. NOTE ** This section is based on the products of Dor-O-Matic, which is located at:
  6. NOTE **    7530 W. Wilson Avenue
  7. NOTE **    Harwood Heights, IL  60656-4786
  8. NOTE **    Tel:  (708) 867-7400
  9. NOTE **    Tel:  (800) 543-4635
  10. NOTE **    Fax:  (708) 867-0291
  11.  
  12. NOTE ** Dor-O-Matic is one of the oldest, most experienced, and most innovative manufacturers of automatic door equipment in the world.  This section covers only a part of their product line:  "Astro-Swing" fire door operators, with accompanying latches, control panels, controls, and accessories, including necessary connecting hardware.  See their other sections for automatic swinging doors, automatic sliding doors, automatic folding doors, and low-energy door operators.
  13. NOTE ** 
  14. NOTE ** SECTION 08747 - FIRE DOOR OPERATORS, Copyright 1998, The Architect's Catalog, Inc.
  15.  
  16. PART 1    GENERAL
  17.  
  18. 1.1    SECTION INCLUDES
  19. NOTE ** Select paragraphs below applicable to project.
  20.  
  21.     A.    Fire door operators for simultaneous pairs of doors, with surface-applied rod panic exit devices.
  22.  
  23.     B.    Fire door operators for simultaneous pairs of doors, with surface-applied rod panic exit device latch releases.
  24.  
  25.     C.    Fire door operators for simultaneous pairs of doors, with concealed rod panic exit devices.
  26.  
  27.     D.    Fire door operators for simultaneous pairs of doors, with concealed rod panic exit device latch releases.
  28.  
  29.     E.    Fire door operators for double-egress sets of doors, with surface-applied rod panic exit devices.
  30.  
  31.     F.    Fire door operators for double-egress sets of doors, with surface-applied rod panic exit device latch releases.
  32.  
  33.     G.    Fire door operators for double-egress sets of doors, with concealed rod panic exit devices.
  34.  
  35.     H.    Fire door operators for double-egress sets of doors, with concealed rod panic exit device latch releases.
  36.  
  37. 1.2    RELATED SECTIONS
  38. NOTE ** Delete sections below not relevant to this project; add others as required.
  39.  
  40.     A.    Section 03300 - Concrete:  Floor recess for carpet.
  41.  
  42.     B.    Section 04200 - Unit Masonry.
  43. NOTE ** Verify that doors will be butt hung; A or B labeled for double egress doors, B labeled for simultaneous pairs (doors swinging in same direction).  Head frame and side jamb widths must be 5-3/4 inches (146 mm) minimum, 12-3/4 inches (324 mm) maximum.  Verify that operator door arms allow fire doors to swing to full corridor width without the need to pocket arms in side walls.
  44.  
  45.     C.    Section _____ - ____________:  Doors and frames.
  46. NOTE ** Verify that two sets of UL-listed panic exit hardware (Von Duprin, Russwin, or Corbin) are specified for each opening to receive fire door operators.
  47.  
  48.     D.    Section 08710 - Door Hardware.
  49. NOTE ** Verify the following electrical provisions.
  50.  
  51.     E.    Division 16 - Electrical:  115 V, 60 Hz., single-phase, 15 amp supply to control panel and from control panel to header; 24 V, NEC Class II wiring from control panel to fire control system and from header to carpet and/or manual controls.
  52.  
  53. 1.3    REFERENCES
  54.  
  55.     A.    ANSI A156.10 (BHMA 1601) - American National Standard for Power-Operated Pedestrian Doors.
  56.  
  57.     B.    ANSI/BHMA A156.19 - American National Standard for Power Assist & Low-Energy Power-Operated Doors.
  58.  
  59.     C.    NFPA 80 - Fire Doors and Fire Windows.
  60.  
  61.     D.    NFPA 101 - Safety to Life from Fire in Buildings and Structures.
  62.  
  63.     E.    UL - Underwriters Laboratories, Inc.
  64.  
  65. 1.4    PERFORMANCE REQUIREMENTS
  66.  
  67.     A.    Operation:  Electric power open, spring close.
  68.         1.    Normal:  Operators instantly recycle to full-open position from any point in closing cycle; motor stops when door is in open position.
  69.         2.    Power Failure:  Doors operate manually as though equipped with manual door closers, without damage to automatic door components.
  70.         3.    Entrapment Protection (Forces and Speeds of Power Opening, Manual Opening, and Spring Closing):  Conform to requirements of ANSI A156.10 (BHMA 1601).
  71.  
  72.     B.    Gear Box Operator:  Allowing easy access to adjustable back check and latching.
  73.  
  74.     C.    Operating Sequence:
  75.         1.    Automatic Operation:  Latching device electrically held in retracted position; panic exit hardware held in unlatched position; doors function normally in automatic mode.
  76.         2.    Operation During Fire or Power Failure:  Signals generated by either power failure or heat and smoke detectors extend latching device on to panic device latch trigger, tripping panic exit hardware into latched position at top and bottom; operator de-energized; springs close doors.  Doors open manually by pushing panic device crossbar, close, and latch automatically by virtue of panic exit hardware.
  77.         3.    Resetting Automatic Operation when Power is Restored:  Pressing system reset button on control panel returns latching device to retracted position and reinstates power to automatic door operator; panic exit device is reset to automatic mode by pushing panic device crossbar on each door.
  78.  
  79. 1.5    SUBMITTALS
  80.  
  81.     A.    Submit under provisions of Section 01300.
  82.  
  83.     B.    Product Data:  Manufacturer's catalog data, detail sheets, and specifications.
  84.  
  85.     C.    Shop Drawings:  Prepared specifically for this project; show dimensions of operators and interface with other products.
  86.  
  87.     D.    Operating and Maintenance Data:  Operating and maintenance instructions, parts lists, and wiring diagrams.
  88.  
  89. 1.6    QUALITY ASSURANCE
  90.  
  91.     A.    Installer Qualifications:  Factory-trained, with minimum 3 years experience.
  92.  
  93.  
  94. PART 2    PRODUCTS
  95.  
  96. 2.1    MANUFACTURERS
  97.  
  98.     A.    Acceptable Manufacturer:  Provide products made by Dor-O-Matic, 7350 West Wilson Avenue, Harwood Heights, IL 60656-4786.  ASD.  Tel: (708) 867-7400 or (800) 543-4635.  Fax: (708) 867-0291.
  99.  
  100.     B.    Requests for substitutions will be considered in accordance with provisions of Section 01600.
  101. NOTE ** Delete paragraph above or below;  coordinate with Division 1 requirements.
  102.  
  103.     C.    Substitutions:  Not permitted.
  104.  
  105.     D.    Provide all fire door operators from a single manufacturer.
  106.  
  107. 2.2    EQUIPMENT
  108.  
  109.     A.    General:  UL listed, meeting provisions of NFPA 80 and 101.
  110.  
  111.     B.    Operators:  "Astro-Swing" surface-applied, self-contained electro-mechanical units mounted in 4-1/2 inch by 5-3/4 inch (114 x 146 mm) aluminum cases.
  112.         1.    Mounting:  Above door.
  113. NOTE ** Select finish from the three paragraphs below.
  114.         2.    Finish:  AIRI clear anodized satin finish.
  115.         3.    Finish:  Color anodized to match doors and frames.
  116.         4.    Finish:  _______________.
  117.  
  118.     C.    Motor: Direct current permanent magnet direct-drive type with shielded ball bearings.
  119.  
  120.     D.    Gear Box:  Complete self-contained cast aluminum housing, fully assembled and sealed; precision-machined gears, precision-machined bearing seats, and shielded bearings; special lubricant for operation from -30 degrees F to 140 degrees F (-34 to 60 degrees C).
  121.  
  122.     E.    Motor/Gear Box Operator:  Mounted on vibration isolators.
  123.  
  124.     F.    Microswitch Box:  Located permanently on bottom of gear box operator; adjustable back check and latching position cams easily accessible without removing door or operator.
  125.  
  126.     G.    Electric Solenoid Latches (Electric Releases):  Housed in operator case for serviceability, not in door frame.
  127. NOTE ** Actuating controls may be selected from any or a combination of the following three paragraphs.  Consult the manufacturer for selection to suit the project.
  128.  
  129.     H.    Control Box:  Snap-in type; full access to adjustments for opening speed, back check speed, closing speed, and time delay; access to fuses and overload protection at bottom without removing control box or door.
  130.         1.    Opening Speed:  Adjustable within safe limits to meet traffic requirements.
  131.         2.    Time Delay:  Adjustable from 2 to 30 seconds.
  132.         3.    Hold-Open Voltage:  Fixed, factory pre-set.
  133.         4.    Soft Start Acceleration Drive and Torque Limiting Drive:  Limit door opening force.
  134.         5.    DC Current to Motor:  Derived by solid state components from 115 VAC power source requiring no more than 5 amps.
  135.         6.    Control Box Electronics:  Switching motor load current to protect relay contacts from premature failure (relay contacts shall not switch motor load current to provide motor control).
  136.  
  137.     I.    Carpet:  Dor-O-Matic molded vinyl, hermetically sealed, 1/2 inch (13 mm) construction, containing steel switch plates, 24 V, NEC Class II wiring to header; meet requirements of ANSI A156.10, Section 4.
  138.  
  139.     J.    Manual Controls:
  140. NOTE ** Select type of manual control(s) from paragraphs below.
  141.         1.    Push Button Switch:  ______________________.
  142.         2.    Push Plate Switch:  ______________________.
  143.         3.    Explosion-Proof Push Plate Switch:  _________________.
  144.  
  145.         4.    Pull Cord Switch:  ______________________.
  146.         5.    Floor Button Switch:  ______________________.
  147.         6.    Explosion-Proof Pull Cord Switch:  ____________________.
  148.  
  149.  
  150. PART 3    EXECUTION
  151.  
  152. 3.1    EXAMINATION
  153.  
  154.     A.    Verify that door openings and doors are properly installed and ready for installation of fire door operators.
  155.  
  156.     B.    Verify that electrical service is available, properly located, and of proper type.
  157.  
  158. 3.2    INSTALLATION
  159.  
  160.     A.    Install in accordance with manufacturer's instructions; comply with ANSI A156.10 and A156.19.
  161.  
  162.     B.    Verify that electrical connections are made correctly.
  163.  
  164. 3.3    ADJUSTING AND CLEANING
  165.  
  166.     A.    Adjust fire door operators for proper operation, without binding or scraping and without excessive noise.
  167.  
  168.  
  169.     END OF SECTION